DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance for csi systems
1-119ATM Tips
1
Figure 1-48. Screen output for the test board 2a01 command
The Result should be PASS for eac h test number. If the any of the
tests fail, refer to ‘‘ATM-BCH (ATM B-Channel Trunk)’’.
Possible Causes
1. The TN230X board is in a slot different from the DEFINITY administration.
2. The TN230X did not complete board insertion.
Physical Layer
Is there an optical signal between the TN230X and the A500?
1. Does the TN230X’s yellow LED flash 100ms on/100ms off, indicating a loss
of signal on the fiber? Recall that the TN230X detects continu ity problems
with either the Transmit (bottom) or the Receive (top) fibers.
2. Is the A500 port’s CD LED off, indicating a loss of sig nal on the fiber? Note
that the A500 detects conti nuity problems only with the Receive
(right-hand) fiber; the state of the Transmit (left-hand) fiber is not d etected.
3. Enter show signaling summary on the A500 console. Figure 1-49 shows
the screen output.
test board 2a01
TEST RESULTS
Port Maintenance Name Alt. Name Test No. Result Error Code
02A01 ATM-EI 316 PASS
02A01 ATM-EI 598 PASS
02A01 ATM-EI 1258 PASS
02A01 ATM-EI 241 PASS
02A01 ATM-EI 304 PASS
02A01 ATM-EI 1259 PASS