DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-33ADX16A-PT (AUDIX Analog Line/Control Link)
3
1003 ABORT The system could not allocate a tone receiver for the test. The system may be
oversized for the number of tone detectors present or some tone detectors may
be out-of-service.
1. Resolve any “TTR-LEV” errors.
2. Resolve any “TONE-PT” errors.
3. If neither condition exists, retry the command at 1-minute intervals a
maximum of 5 times.
1004 ABORT The port was seized by a valid call during the test. The test has been aborted.
Use the display port PCSSpp command to determine the station extension.
Use the status station command to determine the service state of the port. If
the port is in use, wait until the port is idle before testing.
1. Retry the command at 1-minute intervals a maximum of 5 times.
1018 ABORT Test disabled by administration. To enable the test for the particular analog
station being tested, enter the change station <extension> command and
change the ‘‘Test?’’ field on the Station Form from ‘‘n’’ to ‘‘y.’’
2000 ABORT Response to the test request was not received within the allowable time period.
2100 ABORT Could not allocate the necessary system resources for this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
FAIL The reflective Loop Around Test failed. This causes noisy or unreliable
connections or other users calling this port may hear an echo.
1. Replace the circuit pack.
PASS The port is able to provide an analog transmission path to the station
equipment. User-reported troubles on this port should be investig ated by using
other port tests, by examining station wiring, or by examining the station.
Table 3-14. TEST #161 Loop Around Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page