DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-1119TIE-TRK (Tie Trunk)
3
Tie Trunk Seizure Test (#73), Tie Trunk Dial Test (#747). Seizure Test(#73)
The Tie Trunk Seizure Test activates the M lead and chec ks for a response from
the external end within 10 second s. This test is applicable only to wink s tart and
delay dial outgoing trunks. (For the TN2140B circuit pack, the trunk must also be
continuous-seize-ack and discontinuous-seize-ack).
The Tie Trunk Dial Test seizes the trunk and outpulses a p ause digit.
For a port administered as TGU or a TGE, the Seizure Test internally seizes the
trunk and outpulses a "pause." The report reports the result of the seizure attemp t
uplink.
0NO
BOARD The test could not relate the internal ID to the port (no board).
1. Check to ensure that the board translations are correct. Translate the
board, if necessary.
2. Issue the busyout board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board command. This should re-establish the linkage
between the internal ID and the port.
Table 3-493. TEST #36 Audit Update Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page