DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-380CO-DS1 (DS1 CO Trunk)
3
Table 3-168. TEST #7 Conference Circuit Test
Error
Code
Test
Result Description/ Recommendation
ABORT System resources required for this test are not available.
1. Retry the command at 1-minute intervals a maximum of 5 times.
1000 ABORT The test was aborted. System resources required to run this test were not
available. The port may be busy with a valid call. Use the display port
PCSSpp command to determine the trunk group/member number of the
port. Use the status trunk command to determine the service state of the
port. If the service state indicates that the port is in use, then the port is
unavailable for certain tests. You must wait until the port is idle before
retesting.
1. If the port status is active but the port is not in use (no calls), check the
error log for error type 1025 (see the error log table for a description of
this error and required actions). The port may be locked up.
2. If the port status is idle, retry the command at 1-minute intervals for a
maximum of 5 times.
1002 ABORT The test was aborted. The system could not allocate time slots for the test.
The system may be under heavy traffic conditions, or it may have time slots
out of service due to TDM-BUS errors. Refer to the TDM-BUS (TDM bus)
maintenance documentation to diagnose any active TDM-BUS errors.
1. If the system has no TDM-BUS errors and is not handling heavy traffic
and the port status is idle, retry the command at 1-minute intervals for
a maximum of 5 times.
1003 ABORT The system could not allocate a tone receiver for the test. The system may
be oversized for the number of tone detectors present or some of the tone
detectors may be out of service. Issue the list measurements
tone-receiver command to display basic information about the system’s
tone receivers.
1. Look for TTR-LEV errors in the error log. If present, refer to the TT R-LEV
maintenance documentation.
2. Look for TONE-PT errors in the error log. If present, refer to the
TONE-PT maintenance documentation.
3. If neither condition exists, retry the test at 1-minute intervals for a
maximum of 5 times.
1004 ABORT The port has been seized by a user for a valid call. Use the status station
or status trunk command to determine when the port is available for
testing.
1. Retry the command at one-minute intervals a maximum of five times.
2. If the test continues to abort, and the port is not in use, escalate the
problem.
Continued on next page