DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-964PRI-CDR/SEC-CDR (PRI-CDR Link)
3
Notes:
a. System Technician has busied out the CDR link to out-of-service state. The
CDR link is torn down.
b. Link Retry Test (#215) fails. The Aux Data field contains either the Channel
ID of Data Channels on the TN798 Processor circuit pac k (that is, 3 for
Channel 01, 4 for Channel 02, 5 for Channel 03, 6 for Channel 04, and 9
for EIA port) or an Error Code of 99 indicat ing that no data channels are
available for setting up the link, or an Error Type of 255 indicating an
internal system error. Refer to the preceding ‘‘Procedures for Restoring the
CDR Link’’ for resolution.
c. The CDR physical link is down due to the following causes: cab le to the
CDR output device is disc onnected; CDR output devic e is powered off,
the data extension where the CDR output devic e connects to has been
busied out or there is a sched uled daily interchang e. The Aux Data field
contains the Channel ID of Data Channels on the TN798 Processor circ uit
pack (that is, 3 for Channel 01, 4 for Channel 02, 5 for Channel 03, 6 for
Channel 04, and 9 for EIA port). Check the c onnectivity of wire and cab le
among wall jacket, data mod ule, and the CDR output device. Enter status
data extension and verify that the data extension of the CDR output
device is in the in-service/i dle state. If the data extension is not availab le,
then refer to the preceding ‘‘Procedures for Restoring the CDR Link’’ for
resolution. Issue the display system-parameters-maintenance
command to see the start time of d aily maintenance. If the error occurs
and is resolved during the interval of daily maintenance, then the error can
be ignored.
1025 (d)
1281 (e)
1. The MTP Reset Test (#101) logs you off. The MTP Dual Port Ram Test (#104) can also log you off.
Manually repeat the command with the ‘‘long’’ option for the designated number of times when
testing from the PPN SAT.
2. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
3. Minor alarms on this MO may be downgraded to Warning alarms based on the value used in the
set options command.
Table 3-420. CDR Link Maintenance Error Log Entries — Continued
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value1
Continued on next page