DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-767MAPD-BD (MAPD Interface Circuit Pack TN802)
3
NOTE:
Local restore of a complete system from the PCMCIA d isk should not
require more than 20 minutes assuming that a repl acement MAPD pack is
available and pre-load ed with the IP trunk applic ation software.
Restoring data from the PCMCIA diskBefore you start
1. Shut down the application runni ng on the circuit pac k. See ‘‘Shutting down
NT on the TN802’’.
2. Remove the defective IP Trunk circuit pack from the switc h (if applicab le).
3. Install the replacement IP Trunk circuit pack i n the switch (if applic able).
4. Insert the backup d iskette into the IP Trunk circuit pack.
3. Select utility In the IP Trunk Backup/Restore Utility dialog
screen, click on Files, Backup.
The IP Trunk Backup screen appears.
4. Select backup In the IP Trunk Backup screen, click on the
Backup button
5. Wait Backup can take as much as 20 minutes to
complete.
6. Release circuit pack At the DEFINITY ECS terminal type release board
UUCss (the address of the TN802 circuit pack)
and press Enter.
Table 3-321. Backing up TN802 administration data — Continued
Step Description Comments
Continued on next page