DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-940PPP-PT (Control LAN Packet/Port)
3
2100 ABORT Could not locate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals, up to 5 times.
2. Escalate if the problem persists.
2500 ABORT Internal system error.
1. Retry the command at 1-minute intervals, up to 3 times.
2. Escalate if the problem persists.
FAIL PPP link is down.
1. Test the port (test port UUCSSpp long) to verify the SCOTCH
Synchronous Local Loop Around Test (#1275) result.
2. If the test passes, wait for sessions to come up.
3. If the test fails, check the destination and other components in the path
(e.g., DS1 trunks).
4. If the destination and other comonents in the path are in-service and
the test still fails, execute busyout port UUCSSpp and release port
UCCSSpp, and repeat the test.
5. If the test still fails, reset the circuit pack (busyout board UUCSS, reset
board UUCSS, and release board UUCSS). Repeat the test.
6. If the problem persists, replace the circuit pac k.
PASS PPP link is up.
Table 3-405. TEST #1279 PPP Link Status Inquiry Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page