Maintenance Objects
3-781MAPD-BD (MAPD Interface Circuit Pack TN802)
3
2. Completely remove the MAPD-BD from the system:
a. Shut down NT (see ‘‘Shutting down NT on the TN802’’)
b. Remove any administered DS1 trunks, acc ess endpoints, or
PRI endpoints associated with the c ircuit pack from their
respective trunk group s.
c. Remove the DS1 (remove ds1 UUCSS) and circuit p ack
(change circuit pack UUCSS) administration.
If the circuit pac k is properly administered and the red LED is still on,
follow the instructions for LED Alarms with Error Type 1 in Chapter 7.
b. Error Type 2: NT is down and the system attempts to reset the board. If the
reset fails, the board is prob ably bad.
1. Replace the circuit p ack.
c. Error Type 18: the circuit pack has b een busied out.
1. Release the board (release board UUCSS).
d. Error Type 23 and 1025: the MAPD-BD circuit pack is not completely
administered. In add ition to insertion, the MAPD circuit pack mus t have all
of the following administration:
Have an entry in the circuit pl an (change circuit pack)
Be administered as DS1 (add ds1 UUCSS)
The MAPD circuit pack differs from others in that inserting it into the switch
backplane is not enoug h to make the board usab le.
e. Error Type 125, no Aux Data: A wrong circuit pack is in serted in the slot
where this circuit pac k is logically administered . To resolve this problem,
either:
1. Remove the wrong circuit pac k and insert the logic ally
administered circui t pack, OR
2. Re-administer this slot (change circuit-pack) to matc h the circuit
pack inserted.
f. Error Type 257: this error is associated with the Common Port Circuit Pack
Maintenance Test. Refer to XXX-BD (Common Port Circuit Pack)
Maintenance documentatio n for details.
g. Error Type 513: transient hardware problem.
Aux Data:
4352 External RAM failure
4353 Internal RAM failure
4355 Internal ROM failure