DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-662EXT-DEV ADMIN? N (External Device Alarm)
3
EXT-DEV ADMIN? N (External Device Alarm)
NOTE:
Use this Maintenance Objec t when the External Device Alarm
Admin? field on the

change system-para meters customer-options

form is
set to n.
The Processor in carrier A monitors the EXT-DEV alarm leads. The system only
recognizes pairs c onnected to the 1M and 1m (ALARM MONITOR) leads. Refer
to the

DEFINITY Communications System Generic 1 and Generic 3i Wiring,

555-204-111, for more details.
Hardware Error Log Entries and Test to Clear
Valu es
MO Name (in
Alarm Log)
Alarm
Level Initial Command to Run1
1. Where P is an appropriate cabinet number determined via the PORT field from the Alarm
or Error Log.
Full Name of MO
EXT-DEV MAJOR test environment P External Device Alarm
EXT-DEV MINOR test environment P External Device Alarm
Table 3-275. Hardware Error Log Entries and Test to Clear Values
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
01
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
0 Any Any Any test environment UU r2 or
6
1 or 5 Any External Device
Alarm Test (#120) MAJOR
MINOR2
2. One port generates a MAJOR alarm; the other port generates a MINOR alarm.
OFF test environment UU r 2 or
6