DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-1045TBRI-PT (TN2185 ISDN Trunk-Side BRI Port)
3
Level 1 Status Inquiry Test (#1242)
This test is nondestructive. This test determines the state of the tr ansmission
facility of a BRI port at the Level 1 (L1) p hysical layer: Activated , Pending
Activation, or Deactivated.
The Activated state is the correc t state for an ISDN-BRI port. In this state the L1
interface can send and receive synchronized signals. This test passes if the state
of L1 is Activated. This test also passes if software has ta ken this port out of
service. See the descriptio n of the L1 “Deactivated State” b elow for more details.
The Pending Activation state indic ates a problem with the channels, the wiring , or
the TBRI-BD circuit pack. When in this state, the Level 1 inter face is either not
receiving any L1 framing from the channel, or it is communic ating with the
channel or adjunct b ut cannot transition to the Acti vated state.
Table 3-463. TEST #625 Receive FIFO Overflow
Error Counter Test
Error
Code
Test
Result Description/ Recommendation
2000 ABORT Response to the test was not received from the circuit pack within the
allowable time period.
1. If the test aborts repeatedly a maximum of 5 times, reset the circuit
pack with the busyout board PCSS and reset board PCSS
commands.
2. If the test aborts again, replace the circuit p ack.
2012 ABORT Internal system error
2100 ABORT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
value FAIL The TBRI-BD circuit pack is still detecting errors of this type. The Error
Code field contains the value of this counter.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2. If the test continues to fail, run the Long Test Sequence and pay
particular attention to the Looparound Tests (#618 and #619). See the
repair procedures for the executed test if it fails. Otherwise, go to the
next step.
3. Replace the circuit pack.
PASS The Receive FIFO Overflow error counter was read correctly and has a
value of 0.
Continued on next page