DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-164ATM-EI (Expansion Interface Circuit Pack)
3
1394 ABORT 1. See Table 3-65 (Error Type 1281) with Aux Data 27 (board cannot
talk to the ATM switch), and if present, check both the ATM switch
and the DEFINITY administrations for consistent ATM addresses.
2. Reset the board and see if the problem resolves.
3. Repeat the test.
1395 ABORT This test cannot run on an ATM-EI circuit pack if it is part of the B-side
PNC and Duplicated PNC is not enabled.
1. If this test needs to run on this ATM-EI circuit pack, enable PNC with
the change system-parameters duplication command.
2. Prevent the system from doing a PNC interchange by executing the
set PNC lock command.
3. Repeat this test.
1413 ABORT This test requires the use of a Tone/Clock circuit pack in each of the port
networks (PN) used in this test. This abort code indicates that a
Tone/Clock circuit pack is not present in one of the PNs.
1. Make sure that there is a Ton e/Clock circuit pack located in the PN in
which the ATM PNC Expansion Interface circuit pack under test is
located.
2. In ATM PNC configurations, make sure that ther e is at least one oth er
PN besides the PN where the ATM-EI circuit pack under test resides
that contains a Tone/Clock circuit pack.
1414 ABORT The active Tone/Clock circuit pack in one of the port networks being
used for the test has a MAJOR or MINOR alarm logg ed against it.
1. Enter display alarms and resolve any TONE-BD and TONE-PT
alarms.
1956 ABORT ACL to the board is not up. See ACL status with the list sys-link
comma nd and follow t he repa ir proc edure s for SYS-LI NK.
2000 ABORT Response to the test request was not received within the allowable time
period.
2100 ABORT System resources required to run this test are not available.
2500 ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 3 times.
FAIL The test tone was not detected correctly in either direction.
1. Test the active Tone/Clocks on the Port Networks for which the
ATM-EI circuit pack under test provides a link. This determines if the
dial tone is supplied.
Table 3-67. Expansion Interface 2-way Transmission Test (#241) — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page