DEFINITY ECS Release 8.2 Maintenance for R8.2csi
555-233-119 Issue 1
April 2000
Maintenance Objects
3-701HYB-LINE (Hybrid Line)
3
Hybrid Line Audits Test (#61)
This is a series of three tests that are classified as audi ts. These audits abort if
attempted on an out-of-servic e station. The tests are as follows:
Switchhook Audit - This is an update of the SPE records according to the
circuit p acks’ rec ords.
Bad Scan Inquiry - A messag e is sent uplink that contains a c ount that is
generated due to c ertain events relating to the d ata link conditions. This is
an indication of data transm ission problems between the Hybrid circuit
pack and the voic e terminal.
EPF Inquiry - The status of the Electronic Power Feed is sent uplink.
Possible conditions are: EPF-on-ok, EPF-off, EPF-no-load, and
EPF-on-overcurrent.
0NO
BOARD The test could not relate the internal ID to the port (no board). This could
be due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the list
config command, and resolve any problems that are found.
2. If the board was found to be correctly inserted in step 1, issue the
busyout board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command. This should re-establish the
linkage between the internal ID and the port. If this is not the case,
dispatch to check to ensure that there is a valid board inserted.
Table 3-295. TEST #60 Hybrid Line Lamp Updates Test — Continued
Error
Code
Test
Result Description/ Recommendation