Maintenance Object Repair Procedures

9-365CABINET (Cabinet Sensors)

9
Cabinet Temperature Query Test (#122)

This te st qu eries the SYSAM in a PPN o r the EPN Maint enance circuit p ack in an

EPN for the status of the temperature and fan sensors in the cab inet.

Emergency Transfer Query Test (#124)4XXND
Cabinet Temperature Query Test (#122) X X ND
External Alarm Lead Query Test (#120)5XXND
Analog Ring Generator Initial Test (#117)6XXND
Analog Ring Generator Query Test (#118)6XXND
1. See the POWER section in this chapter.
2. See the AC-POWER section in this chapter.
3. See the CARR-POW section in this chapter.
4. See the EMG-XFER section in this chapter.
5. See the EXT-DEV section in this chapter.
6. See the RING-GEN section in this chapter.
Table 9-158. TEST #122 Cabinet Temperature Query Test
Error
Code Test
Result Description/ Recommendation
1000 ABORT System resources required t o r un test are not available.
1. Retry the command at 1-minute intervals for a maximum of 5
times.
2000 ABORT Response to the test request was not received within the allowable
time period.
1. Retry the command at 1-minute intervals for a maximum of 5
times.
2. If the test continues to abort with error code 2000, check for power
problems with the A carrier (PPN or EPN). Look for and resolve all
AC-POWER and CARR-POW alarms in a multi-carrier cabinet or
DC-POWER alarms in a single-carrier cab inet. Repeat the test.
3. If the test continues to abort with error code 2000, check for and
resolve all SYSAM errors in a PPN or MAINT errors in an EPN.
Repeat the test.
2029
2319
2500
ABORT Internal system error
1. Retry the command at 1-minute intervals for a maximum of 5
times.
Continued on next page
Order of Investigation Short Test
Sequence Long Test
Sequence D/ND*