DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-634DS1-BD (DS1 Interface Circuit Pack)
9
Table 9-254. TEST #1227 ICSU Status LEDs Test
Error
Code Test
Result Description/ Recommendation
ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
1005 ABORT The ICSU Status LEDs test can not be executed for the current configuration.
The test applies only to TN767E or later DS1 circuit packs administered for
24-channel operation (1.544 bit rate).
1. If the circuit pack is a TN767E or later suffix DS1 circuit pack, then retry the
command.
1951 ABORT The ICSU Status LEDs T est can not be executed because a 120A1 or later suffix
CSU Module is not physically installed. If using a 120A1 CSU Module,
physically connect it to the TN767E board on the back of the port carrier
otherwise, ignore this ab ort.
2100 ABORT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
2500 ABORT Internal system error.
1. Retry the command.
PASS The ICSU Status LEDs test executed successfully. A PASS result, however,
does not necessarily mean that the status LEDs behaved properly. It only
means that the software successfully attempted to light the status LEDs. This is
a visual test. The service technician must visually exam the behavior of the
LEDs while the test is running. The LEDs are functioning properly if the four
status LEDs are lit red for 5 seconds, then lit green for 5 seconds, then lit yellow
for 5 seconds. If the LEDs behave differently, the board should be replaced at
the customer’s convenie nce.