DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-6AC-POWER
9
Table 9-2. TEST #78 Power Query Test
Error Code Test
Result Description/Recommendation
1000 ABORT System resources required t o r un test are not available.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
100
2000 ABORT Response to the test request was not received within the allowable time
period.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
2. If the test continues to ABORT with error code 2000, check for
system powering problems with the A carrier (PPN or EPN). Resolve
all AC-POWER and CARR-POW alarms. Then, repeat the test.
3. If the test continues to ABORT with a 2000 error code, check for and
resolve all SYSAM errors in a PPN or MAINT errors (EPN
maintenance circuit pack) in an EPN. Then, repeat the test.
2029 2319
2320 2500 ABORT Internal system error
1 FAIL NOTE:
For a J58890CE, skip to step 2.
1. Procedures for a Global MCC (J58890CH):
a. For a nominal holdover system if there is no AC power at the wall
outlet, have a qualified electrician restore power to the outlet.
Power should range from 170 to 264 VAC.
b. If there is AC power at the wall outlet, then there could be a
problem with the RM0850 Rectifiers, BU3200A Battery Interface
Unit (BIU), or battery. Resolve all alarms logged against the
POWER maintenance object, and rerun the test. If the test still
fails, the BIU may be defective. Check the BIU. If the BOD alarm
LED is on, replace the BIU.
If the B OD LED is off and the BOK L ED is on, t hen the SYSAM or
the EPN maintenance circuit pack may be incorrectly reporting
the problem. Resolve all alarms against these MOs and rerun
the test.
Continued on next page