DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures

9-10AC-POWER

9
AC Power Query Test (#78)

This test is not valid for DC-powered cab inets and should always abor t or pass.

Table 9-4. TEST #78 Power Query Test
Error
Code Test
Result Description/Recommendation
1000 ABORT System resources required to run test are not available.
100
2000 ABORT Response to the test request was not received within the allowable time
period.
2029
2319
2320
2500
ABORT Internal system error.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
Any FAIL The SYSAM in a PPN or the EPN Maintenance circuit pack in an EPN is
incorrectly reporting an AC power problem. If this test fails, there is a
problem with the SYSAM OR EPN Maintenance circuit pack. Replace the
suspect circuit pac k and run the test again. (b)
PASS Since this test is invalid for DC-powered cabinets, this result simply
indicates that the SYSAM or EPN Maintenan ce circuit pack is handling this
test properly