DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures

9-187ATM-EI (Expansion Interface Circuit Pack)

9
Figure 9-4. Expansion Interface 2-Way Transmit Test #241PN X and PN Y represent any of 43 possible port networks.
Table 9-80. Expansion Interface 2-way Transmission Test (#241)
Error
Code Test
Result Description/ Recommendation
ABORT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
1002 ABORT The system could not allocate time slots for the test. The system may be
under heavy traffic conditions or it may have time slots out of service due to
TDM-BUS errors.
1. If system has no TDM-BUS errors and is not handling heavy traffic, retry
the command at 1-minute intervals a maximum of 3 times.
1003 ABORT The system could not allocate a tone receiver for the test. The system may
be oversized for the number of tone detectors present, or some tone
detectors may be out of service.
1. Resolve any TTR-LEV errors. Even if there are not TTR-LEV errors, there
may not be a tone detector available on the network that contains the
circuit pack being tested . Verify that there is at least one tone detector
on this network. If not, this test always aborts for this ATM-EI circuit
pack, but does not harm the system.
NOTE:
DEFINITY Systems require that Tone Clock circuit packs (TN2182)
must be of vintage “B” or newer. If older Tone Detector circuit packs
are installed in the system, this test always aborts with this abort
code.
2. Resolve any TONE-PT errors.
3. If neither condition exists, retry the command at 1-minute intervals a
maximum of 3 times.
Continued on next page
Tone
clock
Tone
clock
Tone
detector
Tone
detector
PNCmodePNCmode iodf2wayAWF 040699
ATM
switch
TDMbus
(PNX)
TDMbus
(PNY)
ATM
circuit
pack
ATM
circuit
pack