DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1907UDS1-BD (UDS1 Interface Circuit Pack)
9
Table 9-704. TEST #1227 ICSU Status LEDs Test
Error
Code Test
Result Description/ Recommendation
ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
1005 ABORT The ICSU Status LEDs test can not be executed for the current configuration.
The test applies only to TN464F or later UDS1 circuit packs administered for
24-channel operation (1.544 bit rate).
1. If the circuit pack is a TN464F or later suffix UDS1 circuit pack, then retry
the command.
1951 ABORT The ICSU Status LEDs Test can not be executed because a 120A1 or later
suffix CSU Module is not physic ally installed. If using a 12 0A1 CSU Module,
physically connect it to the TN464F board on the back of the port carrier.
Otherwise, ignore this abort.
2100 ABORT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
2500 ABORT Internal system error.
1. Retry the command.