DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1416SNC-BD (Switch Node Clock Circuit Pack)
9
2303 ABORT The SNC circuit pack responded that the software test requested is not valid.
1. Retry the command at 1-minute intervals a maximum of 3 times.
2304 ABORT SNC circuit pack reponded that it is not able to run the test requested by
software.
1. Retry the command at 1-minute intervals a maximum of 3 times.
2306 ABORT The SNC circuit pack is not responding to test requests sent by software.
1. Run the test led switch-node for the switch node that the SNC resides in
to verify whether the LEDs on the board light.
2. If the LEDs on the other boards in the carrier light, but the LEDs on this
board do not ligh t, run t est 760 via test board UUCSS l for the active SNC
in this carrier. Wait 5 minutes and then try step 1 one more time. If the
LEDs on this board sti ll do not light, replace t his boar d. Repla cing an S NC
may be service interrupting. Refer to the SNC-BD section for the
procedure for replacing an SNC.
3. If none of the LEDs light for the boards in the same carrier as this board, fix
any problems associated with the connectivity of this carrier to the SPE.
Use the list fiber link command to obtain a list of the fiber connections to
this carrier. Check the LEDs on all SNIs and EIs and fix any fiber
problems. Enter display errors and follow the associated repair
procedures for any EXP-INTF error entries associated with the PPN. Also,
follow the associated repair procedures for any SYNC, SNI-BD, SNC-BD,
FIBER-LK, or SNI-PEER error entries.
2500 ABORT Internal System Error
1. Retry the command at 1-minute intervals a maximum of 3 times.
Table 9-555. TEST #780 Switch Node Clock Reset Test — Continued
Error
Code Test
Result Description/ Recommendation
Continued on next page