DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1241PKT-BUS (Packet Bus)
9
2077 ABORT The Maintenance/Test Circuit Pack Query located more than one
Maintenance/Test packet bus port in the port-network.
NOTE:
The software should not allow this to occur. This is an internal system
error. Escalate the problem, but also attempt the following work-around
steps.
1. Remove all Maintenance/Test circuit packs from the port-network.
2. Insert one Maintenance/Test circuit pack (there should not be more than
one in a port-network).
3. Re-enter the test command.
2100 ABORT Maintenance could not allocate all of the necessary system resources to
perform this test.
2500 ABORT An internal operation failed; the test could not be completed.
1. Re-enter the command at 1-minute intervals a maximum of 5 times.
Table 9-495. Test #572 Maintenance/Test Circuit Pack
Query Test — Continued
Error
Code Test
Result Description/ Recommendation