DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-381CARR-POW (Carrier Power Supply)
9
Error Log Entries and Test to Clear Values
!WARNING:
The OLS Recycle Test (#126) is destructive. For more information, refer to the description of this test.
System Technician-Demanded T ests: Descripti ons
and Error Codes
Always investigate tests in the order p resented in the table below. By c learing
error codes associated with the
Battery & Battery Charger Query Test
, for
example, you may also clear errors g enerated from other tests in the testing
sequence.
Table 9-159. Carrier Port Power Supply Error Log Entries
Error
Type Aux
Data Associated Test Alarm
Level On/Off
Board Test to Clear Value
11
1. Run the OLS Query Test (#127) first using the test environment UUr 2 command. Then, if a
carrier must be recycled to clear the CARR-POW alarm, use the recycle carrier UUC command
to run the OLS Recycle Test (#126). T he OL S R ecycle T est (# 126) is not included in either the long
or short test sequences.
0 or 1 OLS Query Test (#127) MAJOR ON test environment
UU
r 2
recycle carrier
UUC