DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1878UDS1-BD (UDS1 Interface Circuit Pack)
9
1 to 17
(cont’
d.)
FAIL
(cont’d.)
If the UDS1 connects to a line-side terminating device such as a PRI terminal
adapter:
1. Retry the command at 1-minute intervals for a maximum of 5 times.
2. Enter the list measurement ds1-log UUCSS command to read the error
seconds measurement.
3. Verify that the switch DS1 and the line-side terminating device are
administered using the same signaling mode, framin g mode, and line
coding.
4. Investigate the maintenance status of the line-side terminating device.
Refer to the ’Line-Side Terminating Device Operatin g Manual’ for
information.
5. Contact the vendor of the line-side terminating device to diagnose the
equipment.
6. Check the physic al connection of the UDS1 interfac e circuit pack to the
terminating device, and check the premise di strib ution system (or the
intra-premise wiring) for p hysical connection fa ilures.
7. Replace the local UDS1 interface circuit pack and repeat the test.
PASS No Misframe alarm is detected on the UDS1 Interface circuit pack.
0NO
BOARD The test could not relate the internal ID to the port (no board). This could be
due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane b oard is inserted.
1. Ensure that the board translations are correct. Execute the add ds1
UUCSS command to admini ster the UDS1 interface if it is not already
administered.
2. If the board was already administered correctly, check the error log to
determine whether the board is hyperactive. If this is the case, the board is
shut down. Reseating the b oard will re-initialize the board.
3. If the board was found to be correctly inserted in step 1, then issue the
busyout board command.
4. Issue the reset board command.
5. Issue the release busy board command.
6. Issue the test board long command.
This should re-establish the linkage between the internal ID and the port.