DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1619SYSAM (Circuit Pack)
9
1339 ABORT The test could not run on the standby SYSAM circuit pack in the standby SPE
carrier because t he standby SPE is unavailable.
1. Refer to the STBY-SPE maintenance documentation for information on
why a standby SPE may be unavailable and what repair actions should
be taken. The screen for the status spe command should indicate that
handshake is down. This may be caused by a variety of reasons such as
the SPE-SELEC T switc hes on the DUPI NT circ uit p ack s bein g set to the
posit ion of the ac tive SPE, a fai lure of the DU PINT cir cuit pac k, or l oss of
power on the standby SPE. The SPE selected field on the status spe
screen displays spe a or spe b if both SPE-SELECT switches are in the
a or b positions, respectively.
1364 A BORT Th e comp onen t on whi ch th e test was to b e run is on t h e Stand by SPE. This
test may only be run on this component when it resides on the Active SPE.
1. To verify the remote access line is working (connected), run this on the
Acti ve SYSAM.
1379 ABORT System could not determine if testing of remote access port is administered.
1. Check system-parameters maintenance screen for a y in the Test
Remote Access Port field.
2. Retry the command.
2000 ABORT Response to the test request was not received within the allowable time
period. If the system is a High or Critical Reliability configuration and if the
SYSAM circuit pack is on the standby SPE, this abort code may indicate that
the standby SPE is not responding to the handshake message. If this is the
case, the standby SPE maintenance software may take up to two minutes to
indicate that handshake communication with the standby SPE is down. The
ABORT code then changes to 1339 (standby SPE unavailable).
1. Retry the command at 1-minute intervals, a maximum of 3 times.
2034 ABORT The remote access port is busy. A remote user is probably dialed into the
switch.
1. Wait until the remote user session is terminated, retry the command.
2317 ABORT Test #916 SYSAM Outpulse Relay Test failed.
1. Follow instructions for FAIL result for SYSAM Outpulse Relay Test (#916).
Table 9-612. TEST #917 SYSAM Analog Looparound Test — Continued
Error
Code Test
Result Description/ Recommendation
Continued on next page