DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1949XXX-BD (Common Port Circuit Pack)
9
Control Channel Looparound Test (#52)
This test queries the circuit p ack for its circuit p ack code and vintage and verifies
its records.
SAKI Sanity Test (#53)
This test is destructive.
This test resets the circuit pack. It is executed as part of the lo ng test sequence
only for the Tone-Clock circuit pack and DS1 interface circuit pac ks. Other
common circuit p acks can be reset with the reset board UUCSS command
which also executes this test.
Table 9-723. TEST #52 Control Channel Looparound Test
Error
Code Test
Result Description/ Recommendation
None
2100 ABORT System resources required for this test are not available.
1. Retry the command at 1-minute intervals a maximum of 5 times.
FAIL The test failed because the circuit pack failed to return the circuit pack c ode or
vintage.
1. Retry the command for a maximum of 5 times.
2. If the test still fails, issue the busyout board, reset board, and release
busy board commands, and then retest.
3. If the problem continues, replace the circuit p ack.
4. Run the test again.
PASS Communication with this circuit pack is successful.
EXTRA
BD This result should only appear when more than one TN771D Maintenance/Test
circuit pack has been installed in this port network. Remove this circuit pack.
Any NO
BOARD This is normal if the test is being done when (a) the board is not physically in the
system or (b) the system is booting up. Otherwise, there is some inconsistency
between the physical configuration and the data kept in the system.
1. Verify that the board is physically in the system.
2. Verify that the system is not in a stage of booting up.
3. Retry the command at 1-minute intervals for a maximum of 5 times.
Continued on next page