DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-715DUP-CHL (Duplication Interface)
9
Table 9-277. TEST #874 Duplication Channel Test
Error
Code Test
Result Description/ Recommendation
1321 ABORT The faceplate switches on the Duplication Interface circuit pac ks are not set to
auto.
1. If the switches are locked because you are using a replacement
procedure, continue with this procedure to the step that directs you to
unlock the active SPE by moving both switches to auto. The next step
using the test duplication-interface long clear should not abort with this
error code.
2. If the switches are locked and a replacement proced ure is not being used,
start with st ep 6 of the SPE Dup lic ation C hannel Comp onent Re plac ement
procedure for the standby Duplication Interface Circ uit pack at the end of
this DUP-CHL section to avoid an undesired interchange when unlocking
the active SPE.
3. If this same abort is received with both switches in auto, Replace
Duplication Interface components starting with the standby Dup lic ation
Interface circuit pack. Use SPE Duplication Channel Component
Replacement procedures at the end of this DUP-CHL section. In addition to
looking for failures, also check for the absence of this 1321 abort code
when testing after the procedure directs setting the switches to auto after a
component replacement.
1411 ABORT This test did not run because the standby Duplication Interface c ircuit pack
cannot be detected as b eing plugged in by the software.
1. If this abort continues to occur, the standby SPE may not have initialized
properly. Use the lock-and-power-down procedure desc ribed in Chapter 5
to power down and power up the standby SPE, but don’t replace any
circuit packs.
2000 ABORT This test did not run because communication with the standby timed out while
waiting for a reply to a maintenance message.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2. If this abort continues to occur, the standby SPE may not have initialized
properly. Use the lock-and-power-down procedure desc ribed in Chapter 5
to power down and power up the standby SPE, but do not replace any
circuit packs.
2500 ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
FAIL The standby software did not return the test message sent from the active SPE
to the standby SPE via the Duplication Interface circuit pack mailbox.
1. Replace Duplication Interface comp onents starting with the standby
Dupl icati on Inte rfac e circ uit p ack. Use SPE Dup lica tion C hannel
Component Replacement procedures at the end of this DUP-CHL section.
Continued on next page