DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1061MMI-BD
9
Error Log Entries and Test to Clear Values
Notes:
a. The circuit pack stopp ed functioning or it was p hysically removed from the
system. The alarm logs approximately 11 m inutes after the circuit pack
has been removed and/or the SAKI Sanity Test (#53) fails.
If the circuit pac k is in the system and the red LED is on, follow the
instructions for a red alarm in ‘‘Circui t Pack LEDs’’ in Chapter 7, ‘‘LED
Interpretation’’. Also, see “Handling Common Port Circuit Packs.”
b. This circuit pack h as been busied out using th e busyout board UUCSS
command.
c. There are more than four MMI circuit pac ks in the system. Remove the
circuit pack that generated the error in the error log b y locating the slot
indicated by the error.
Table 9-421. MMI-BD Error Log Entries
Error
Type Aux
Data Associated Test Alarm
Level On/Off
Board Test to Clear Value
01
1. Run the short test sequence first. If all tests pass, run the long test sequence. Refer to the appropriate
test description and follow the recommended proc edures.
0 Any Any Any test board UUCSS sh r 1
1 (a) Any None MIN ON
18 (b) 0 Busyout board UUCSS WNG OFF release board UUCSS
217 (c) 0 None WNG ON
257 (d) 65535 Control Channel Loop Test
(#52) MIN ON test board UUCSS r 3
513 (e) 4352
to
4357
Uplink error from pack
769 (f) Any MMI Synchronization
Status Test #1123
1281 (g) Any Circuit Pack Restart Test
(#594) MAJ ON
1538 (h) Any Software detected error MIN ON
1793 (i) ANY TSI XTalk (#6) MIN ON test board UUCSS l r 3
2049 (j) Any TSI Loop (#1108) MAJ ON test board UU C SS l r 3