DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1322POWER
9
Error Log Entries and Test to Clear Values
Note:
a. This error occurs is valid only for AC-powered multi-carrier cabinets with
battery backup . For DC-powered cabinets, you c annot clear the error and
it should be ignored.
Battery Holdover (Large Batteries)
The large batteries are mounted insid e a separate battery c abinet and can
supply holdover times of 2 to 8 hours depending on the size of the battery. The
batteries are circuit breaker p rotected and are c harged by the J58890CH-1. The
batteries also contain a thermal sensor that change the charg ing voltage
depending o n the battery temperature.
Table 9-514. Battery & Battery Charger Error Log Entries
Error
Type Aux
Data Associated Test Alarm
Level On/Off
Board Test to Clear Value
01
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommend ed procedures.
0 Any Any Any test environment UU sh r 1
1 Any Battery & Battery Charger
Query Test (#5) (error
code 8)
MINOR ON test environment UU s r 1
257 Any Battery & Battery Charge
Query Test (#5) (error
code 4)
MINOR ON test environment UU s r 1
769 Any Battery & Battery Charger
Query Test (#5) (error
code 2)
MINOR ON test environment UU s r 1
3840(a) 1005 or
1028 Associated Battery &
Battery Charger Query
Test (#5)
test environment UU s r 1