DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1908UDS1-BD (UDS1 Interface Circuit Pack)
9
PASS The ICSU Status LEDs test executed successfully. A PASS result, however,
does not necessarily mean that the status LEDs behaved properly. It only
means that the software successfully attempted to light the status LEDs. This is
a visual test. The service technician must visually exam the behavior of the
LEDs while the test is running. The LEDs are function ing properly if the f our
status LEDs are lit red for 5 seconds, then lit green for 5 seconds, then lit yellow
for 5 seconds. If the LEDs behave differently, the board should be replaced at
the customer’s convenie nce.
0NO
BOARD The test could not relate the internal ID to the port (no board). This could be
due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane b oard is inserted.
1. Ensure that the board translations are correct. Execute the add ds1
UUCSS command to admini ster the UDS1 interface if it is not alread y
administered.
2. If the board was already administered correctly, check the error log to
determine whether the board is hyperactive. If this is the case, the board is
shut down. Reseating the b oard will re-initialize the bo ard.
3. If the board was found to be correctly inserted in step 1, then issue the
busyout board command.
4. Issue the reset board command.
5. Issue the release busy board command.
6. Issue the test board long command.
This should re-establish the linkage between the internal ID and the port.
Table 9-704. TEST #1227 ICSU Status LEDs Test — Continued
Error
Code Test
Result Description/ Recommendation
Continued on next page