DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-528DIOD-DS1 (DS1 DIOD Trunk)
9
Table 9-216. TEST #314 DS1 CO Dial Tone Seizure Test
Error
Code Test
Result Description/ Recommendation
ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
1000 ABORT System resources required to run this test are not available. The port may be
in use on a valid call. Use the status trunk command to determine when the
port is available for testing.
1004 ABORT The port has been seized by a user for a valid call. Use the status trunk
command to determine when the port is available for testing.
1. Retry the command at 1-minute intervals a maximum of 5 times.
1005 ABORT Test failed due to in compatible config uration administered in trunk g roup
form.
1. Look at the trunk group ad ministration form and see if the tr unk is
incoming only, port 24 on a DS1 Interface with common control channel
signaling, or an automatic CO type such as FX. Under any of these
conditions this is a normal abort.
1018 ABORT Test has been disabled via administration.
1. Verify that the ‘‘Maintenance Tests’’ field on the Trunk Group Form is set
to ‘‘n.’’ To enable the test, issue the change trunk-group x command
where ‘‘x’’ equals the number of the trunk group to be tested. Then
change the entry in the ‘‘Maintenance Tests’’ field on the form to ‘‘y.’’
2. Repeat the test.
1020 ABORT The DS1 Interface circuit pack is out-of-service.
1. Look for UDS1-BD errors in the Hardware Error Log. If present, refer to
"UDS1-BD (UDS1 Interface Circuit Pack)" (DS1/UDS1 Trunk Circuit
Pack) .
2. Retry the command.
2000 ABORT Response to the test request was not received within the allowable time
period.
2100 ABORT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
Continued on next page