DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1832UDS1-BD (UDS1 Interface Circuit Pack)
9
Notes:
a. Error 1 indicates that the circui t pack has totally stopp ed functioning or is
not fully administered. The alarm is logg ed about 15 minutes after the
circuit pack has been removed or 11-minutes after the SAKI Test (#53)
fails.
To be fully administered, a UDS1 circuit pac k must meet all of these 3
conditions:
1. Have an entry in the circuit p lan via the change circuit pack
command
2. Be administered via the add ds1 UUCSS comm and
3. Be physically inserted into the correct slot
If the circuit pac k has an entry in the circuit plan and either of the other two
conditions are
not
met, a MINOR alarm is logged. To resolve the error
either
3841(y) 4358
3842(z) 46097
3843(aa) 46081
3900(ab) Any CPE Loopback Jack
Test (#1212)
3901(ac) Any Far CSU Loopback Test
(#1213)
3902(ad) Any One-Way Span Test
(#1214)
3999(ae) Any None
1. Run the Short Test S equence first. If all tests pass, run the Long Test Sequence. Refer to the appropriate
test description and follow the recommended proc edures.
2. If ports are assigned to the circuit pack, then a minor alarm is raised. If no ports are assigned to the circuit
pack, then a warning alarm is raised. The alarm is raised after the circuit pack has been missing for a
period of 15 minutes. Warning alarms are also raised against any ports administered on the circuit pack.
3. Minor alarms on this MO may be d owngraded to warning alarms based on values set in the set options
command.
4. Major alarms on this MO may be d owngraded t o minor or warning alarms b ased on values set in the set
options command.
Table 9-681. DS1 Interface Circuit Pack Maintenance Error Log Entries — Continued
Error
Type Aux
Data Associated Test Alarm Level On/Off
Board Test to Clear Value
Continued on next page