DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1279PKT-INT (Packet Interface Circuit Pack)
9
NO
BOARD The Packet Interface circuit pack is administered but is not detected as being
physically present.
1. If the Packet Interface circuit pack is present, replac e it.
2. If the Packet Interface circuit pack is not physic ally present, use the
display system-parameters maintenance command to check if the
Packet Interface circuit pack is administered as being present. If it is
administered, use the change system-parameters maintenance
command to cha nge the Packet Interfac e circuit pac ks administered to b e
those actually present.
NOTE:
If the system is equipped with the High Reliability or Critical Reliability
Configuration, the Packet Interface entry on the system-parameters
maintenance screen will show "y" if translation data is present for a
Packet Interface circuit pack on either the active or standby SPE or if a
Packet Interface circuit pack is present on either the active or standby
SPE. The co rresp ondin g ent ry on th e scre en can only b e cha nged from
"y" to "n" if a Packet Interface circuit pack is not physically present in the
active SPE. However, if the system is restarted with a restart lev el equal
or greater than a WARM restart, the Packet Interface circuit pac k
maintenance software will automatically detect any Packet Interface
circuit pack physically present on the active or standb y SPE and the
corresponding field on the system-parameters maintenance screen will
show a ‘‘y.’’
5001 FAIL The TDM clock on the Processor Port Network has failed.
1. Refer to the “TDM-CLK” to clear this failure.
5002 FAIL The Packet Bus on the Processor Port Network has failed.
1. Refer to “PKT-BUS” to clear this failure.
Table 9-503. TEST #889 Reset Test — Continued
Error
Code Test
Result Description/ Recommendation
Continued on next page