DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1317POWER
9
1005 ABORT The battery charger is not connected. If the system has a UPS, ignore this
error since the batteries and charger are not required.
1. The batteries will probably need charging and may b e drained if there
were power outages. Reconnect the battery charger to allow the batteries
to recharge. If test #5 is run before the batteries are completely charged,
the test will fail.
2. Wait 24 hours and rerun the test.
2000 ABORT Response to the test request was not received within the allowable time
period.
1. Retry the command at 1-minute intervals a maximum of 5 time.
2. If the test continues to ABORT with error code 2000, check for system
powering problems with the A carrier (PPN or EPN). Look for and resolve
all AC-POWER and CARR-POW alarms in a multicarrier cabinet system.
Then, repeat the test.
3. If the test continues to ABORT with a 2000 error code, check for and
resolve all SYSAM errors in a PPN or MAINT (EPN Maintenance circuit
pack) errors in an EPN. Then, repeat the test.
2029
2319
2320
2500
ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
2 FAIL The system is in nominal power holdover, and the battery is currently so low
that the system will disconnect power very shortly.
1. If power returns, then the port carriers in the PPN should power-up again.
All the circuit packs should be reinserted, and the system should c ontinue
to operate normally. There will probably be a minor alarm against Battery
& Battery Charger due to the fact that the batteries are recharging.
2. If power does not return, the system will shut down to prevent damage to
the batteries. Restore power, and the system will reboot.
No manual intervention is required.
3) Rerun the test. If the test still fails, then the
SYSAM in a PPN or the EPN MAINT (Maintenance) circuit pack in an EPN
could be reporting this condition inc orrectly. Resolve all alarms on these
MOs and rerun the test. There are failures that can occur on the SYSAM
and EPN Maintenance circuit pack that
will not
be detected by their
respective maintenance, but which will cause many, if not all, environment
tests to fail. If many environment tests are failing, the suspect circuit pack,
depending on the system configuration, should be replac ed and the test
rerun.
Table 9-513. TEST #5 Battery & Battery Charger Query Test — Continued
Error
Code Test
Result Description/ Recommendation
Continued on next page