DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-861FIBER-LK (Fiber Link)
9
Table 9-333. TEST #759 Configuration Audit
Error
Code Test
Result Description/ Recommendation
2100 ABORT Could not allocate the necessary system resources to run this test for endpoint
1 of the fiber link (list fiber-link can be used to display fiber link endpoints). If
this fiber link has two SNI endpoints, run the test board UUCSS test separately
for each SNI and follow the repair procedures in section SNI-BD.
2300 ABORT The downlink message necessary to run this test could not be sent. If this fiber
link has two SNI endpoints, run the test board UUCSS test separately for each
SNI and follow the repair procedures in section SNI-BD (list fiber-link can be
used to display fiber link endpoints).
2301 ABORT The software timer could not be set before sending the downlink message
necessary to run this test. If this fiber link has two SNI endpoints, run the test
board UUCSS test separately for each SNI and follow the repair procedures in
section SNI-BD (list fiber-link can be used to display fiber link endpoints).
1. Retry the command at 1-minute intervals a maximum of 3 times.
2306 ABORT An SNI circuit pack on the fiber link is not responding to test requests sent by
software.
1. Run the test led switch-node for the switch node(s) that the SNI(s) reside
in to verify whether the LEDs on the board(s) light. Follow the steps below
for the SNI(s) that had no LEDs light.
2. If the LEDs on the other boards in the carrier light, but the LEDs on this
board do not light, run test 760 via test board UUCSS l for the active SNC
in this carrier. Wait 5 minutes and then try step 1 one more time. If the LEDs
on this board still do not light, replace this board. Replacing an SNI may be
service interrupting. Refer to the SNI-BD section for the procedure for
replacing an SNI.
3. If none of the LEDs light for the boards in the same carrier as this board, fix
any problems associated with the connectivity of this carrier to the SPE.
Use list fiber-link to determine the fiber connections to this carrier. Check
the LEDs on all SNI s and EI s and fix any fiber problems. Enter display
errors and r esolve any EXP-INTF e rror ent ries as socia ted wi th the PPN .
Also, resolve any SYNC, SNI-BD, SNC-BD, FIBER-LK, or SNI-PEER error
entries.
2500 ABORT Internal system error If this fiber link has two SNI endpoints, run the test board
UUCSS test separately for each SNI and follow the repair procedures in section
SNI-BD (list fiber-link can be used to display fiber link endpoints). Otherwise:
1. Retry the command at 1-minute intervals a maximum of 3 times.
Continued on next page