DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures
9-1324POWER
9
Table 9-515. TEST #5 Battery & Battery Charger Query Test
Error
Code Test
Result Description/ Recommendation
1000 ABORT System resources required to run this test are not available.
1005 ABORT Battery charger is not connected. DC-powered cabinets do not have battery
backup; ignore this error.
2000 ABORT Response to the test request was not received within the allowable time
period.
2028 ABORT Internal system error prevented the extinguishing of the Battery Charger status
LED.
1. Since this test is not relevant for DC-powered systems, an occurrence of
this error indicates possible existence of internal system problems.
2029
2319
2320
2500
ABORT Internal system error
1. Try the command again at 1-minute intervals up to 5 times.
any FAIL The SYSAM in a PPN or the EPN Maintenance circuit pack in an EPN is
incorrectly reporting a problem with p ower. If this test fails for a DC-powered
cabinet, the circuit pack has a p roblem. Replace the suspect circuit pac k and
run the test again.
PASS A ll that can b e infe r red is that th e SYSAM in a PPN or the EPN Maint enanc e
circuit pack in an EPN in an EPN multicarrier cabinet system is working
properly for this test.