DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126 Issue 4
June 1999
Maintenance Object Repair Procedures

9-1655TAPE

9
Tape Res et Te st (#89 4)

The Tape Reset Test is run on as part of the reset tape command . The test results

for Test 894 are the same as those for Test 809, which is run as part of the test

tape sequence. All tape alar ms are cleared when Test 894 passes, while only

some tape alarms may clear when Test 809 passes. Refer to results for Test 809

for repair procedures.

5102 ABORT Could not allocate the Mass Storage System to run this test
1. Retry the command at 1-minute intervals a maximum of 5 times.
2. If the test continues to abort, verify that the daily translation-save operation
is not in progress (issue the display system-parameters maintenance
command to display the time for scheduled maintenance and the "y/n"
option for saving translation daily).
NO
BOARD The tape has been placed in the "uninstalled" state.
1. Verify that a tape cartridge is installed and not write-protected and that the
tape drive is fully inserted and powered up.
2. Attempt a demand reset of the tape.
1FAIL The tape configuration information shows the tape circuit pack is missing or the
tape LED test failed.
1. Verify that a tape cartridg e is installed and not write-p rotected.
2. If a tape was inserted, remove it and clean the tape heads.
3. If the test continues to fail, replace the Tape Cartridge. Wait for the
retension pass to complete. If the test succeeds, issue the backup disk
command.
4. If the test continues to fail, replace the Tape circuit pack.
5. If the test continues to fail, replace the MSSNET circuit pack.
PASS The Tape status test passed succ es sfully. Check other test results to see if it is
operating correctly.
1. See the MSS Error Actions table at the end of the section on TAPE.
Table 9-623. TEST #815 Tape Status Test — Continued
Error
Code Test
Result Description/ Recommendation
Continued on next page